3 Phase Multi Function Energy Meter Kwh Meter TOKY DS9L

3 Phase Multi Function Energy Meter Kwh Meter TOKY DS9L

3 Phase Multi Function Energy Meter Kwh Meter Toky Ds9l, High Quality Energy Meter,Kwh Meter,3 Phase Kwh Meter
INQUIRY PRECISE INQUIRY
Description

Overview
Quick Details
Place of Origin:
Guangdong, China (Mainland)
Brand Name:
TOKY
Model Number:
DS9L-RC38
Measuring Current Range:
AC 0.025~5A
Measuring Voltage Range:
AC 3X220V / 380V (3X57.7V / 100V)
Accuracy Class:
0.5
Operating Temperature:
-10~50℃
Dimensions:
96H x 96W x 61.5L (mm)
Item:
Energy meter, kwh meter
Display:
segment LCD display
Analog output:
No / 4-20mA
Alarm output:
2 loop
Input signal:
3 phase with communication
Packaging & Delivery
Packaging Details
Standard paper box, one product in one small box, cartons choosing according to the different size of the products.
Delivery Time
Within 7days

3 Phase Multi Function Energy Meter Kwh Meter TOKY DS9L   

 

 

3 Phase Multi Function Energy Meter Kwh Meter TOKY DS9L

 

DS9L Three Phase Energy Meter, Kwh Meter Features:

1)  Measuring Items: 3 phase power network Voltage/Current/Active Power/Reactive Power/Frequency/Power Factor etc, totally 28 parameters.

2) Two ON/OFF input and two ON/OFF output (optional four ON/OFF input )

3) True effective value measurement
4) With RS485 interface,Modbus RTU communication protocol
5) One active energy pulse output
6) With Power fail memory function for Kwh / KvarH

 

 

 

3 Phase Multi Function Energy Meter Kwh Meter TOKY DS9L

 

DS9L Three Phase Energy Meter, Kwh Meter Model:

ModelAlarm or remote controlCommunicationON/OFF input or telecommand
DS9L-RC382RS4852 (optional 4 input)

 

 

 

3 Phase Multi Function Energy Meter Kwh Meter TOKY DS9L

 

DS9L Three Phase Energy Meter, Kwh Meter Specification:

Connection 3 Phase 3 Wires, 3 Phase 4 Wires
Voltage measuring range AC 3×220V/380V (3x57.7V/100V)
Voltage overload Continuous: 1.2 times Instantaneous: 2 times/10S
Voltage consumption <1VA (each phase)
Voltage impedance ≥300KΩ
Voltage accuracy RMS measurement, accuracy class 0.5
Current measuring range AC 0.025~5A
Current overload Continuous: 1.2 times Instantaneous: 10 times/10S
Current consumption <0.4VA (each phase)
Current impedance <20mΩ
Current accuracy RMS measurement, accuracy class 0.5
Freqency 45~60Hz, accuracy 0.01Hz
Power Active / Reactive / Apparent power, accuracy 0.5 class
Energy Active Energy 1 class, Reactive Energy 2 class
Power supply working range AC/DC 100~240V (85~265V)
Power supply consumption ≤5VA
Output digital interface RS-485, MODBUS-RTU Protocol
ON/OFF input 2 ON/OFF input (Connection without voltage or current signal)
Alarm output 2 ON/OFF output, 250VAC/3A or 30VDC/5A (optional, please ask our sales)
Isolation Input/ Output/ Power supply to meter cover>5MΩ

 

 

 

 

3 Phase Multi Function Energy Meter Kwh Meter TOKY DS9L

 

 

DS9L Three Phase Energy Meter, Kwh Meter Connection:

3 Phase Multi Function Energy Meter Kwh Meter TOKY DS9L

 

 

 

 

3 Phase Multi Function Energy Meter Kwh Meter TOKY DS9L

 

 

DS9L Three Phase Energy Meter, Kwh Meter Dimension:

 

3 Phase Multi Function Energy Meter Kwh Meter TOKY DS9L